Specifications DIM20/1, DIM20HR, DIM20/2, DIM35, DIM50 & DIM100 1. The dimming modules shall be the PWR Series DIM20/1, DIM20HR, DIM20/2, DIM35, DIM50, or DIM100 as required by the circuit layout. 2. The modules shall provide control of incandescent loads, as well as magnetic and electronic transformers and ballast that, per the manufacturer of these devices, are suitable for 2 wire, line voltage, phase-forward dimming. 3. The modules shall employ hard-fired solid-state relays that incorporate one or two pairs of silicon controlled rectifiers (SCR) mounted in anti-parallel configuration, a snubber network, gate drive circuitry, and an opto-isolator in industry standard 1.80" x 2.30" or 2.50" x 4.00" packages. Systems utilizing triacs or proprietary SCR packages shall not be acceptable. 4. The solid-state relays shall be UL and cUL recognized and rated for a nominal line voltage of no less than 277Vrms and withstand peak voltages of minimum 600V. The devices shall have a minimum continuous rating of 40, 75, and 150A and shall withstand surge currents, for no less than 16.6ms, of minimum 625, 1000, and 1600A for the 20, 35 & 50, and 100A modules respectively. 5. The modules shall incorporate toroidal chokes providing, with 100% of full rated load, a rise-time of at least 350µs for 20 & 35A circuits and 500µs for 50 & 100A modules. Extended rise-time models and add-on modules shall be available to increase rise-time for 20 & 35A and 50 & 100A circuits to at least 700 and 1000µs respectively. Rise-time shall be measured from 10% to 90% of the waveform amplitude at 90° conduction angle. 6. The modules shall be convection cooled only. An aluminum heat-sink, that forms the main structural member of the module, shall provide no less than 160, 320, and 640 square inches of unobstructed primary cooling surface for the 20 & 35, 50, and 100A modules respectively. Systems utilizing fans or other means of forced primary or supplementary cooling shall not be acceptable. 7. Overall efficiency with standard rise-time shall be no less than 96%. Thermal emission at full rated load shall not exceed 300, 450, 600, 575, 800, and 1600BTU/hr for the 20, 20HR, dual 20, 35, 50, and 100A modules respectively. 8. Output waveform asymmetry and DC component shall not exceed 1% at full rated load. 9. The module load circuit surge and transient withstand capability shall meet or exceed the minimum recommendations of ANSI C64.21-1991. Continuous breakdown voltage between control terminals, load terminals, and ground shall be no less than 4000V. 10. Line and load terminals shall accept up to #8 AWG wire for 20A modules, up to #6 AWG wire for 35 and 50A modules, and up to #1/0 AWG wire for 100A modules. Control wiring shall be provided by a 24" harness factory terminated in a 4 position keyed plug-in header. 11. The modules shall be UL listed for continuous operation at 100% of their rating per NEC 1999 Article 210-20-a. Systems failing to meet this requirement shall not be acceptable. 12. The modules including their wiring, termination points, mounting hardware, enclosure and controller shall be UL and cUL listed as a complete assembly and for Canadian installations comply with CSA Standard C22.2 #14-M91. UL recognized or listed devices alone shall not be acceptable unless documentation is submitted to verify that the entire assembly, including the controller and enclosure, has been tested and evaluated by a Nationally Recognized Testing Laboratory (NRTL) and found to meet all the herein-mentioned standards and requirements. 13. The modules shall be UL and cUL listed for AC lighting loads with the following minimum ratings per circuit at 40°C ambient temperature: DIM20/1 20A, 2400W @ 120V 10A, 2400W @ 240V 10A, 2400W @ 277V DIM20HR 20A, 2400W @ 120V 10A, 2400W @ 240V 10A, 2400W @ 277V DIM20/2 20A, 2400W @ 120V 10A, 2400W @ 240V 10A, 2400W @ 277V DIM35 35A, 4200W @ 120V 17.5A, 4200W @ 240V 17.5A, 4200W @ 277V DIM50 50A, 6000W @ 120V 25A, 6000W @ 240V 25A, 6000W @ 277V DIM100 100A, 12000W @ 120V 50A, 12000W @ 240V 50A, 12000W @ 277V